Certification

IECEx Certificates

Our units are certified as complete assemblies, built from parts that carry their own certificates. Select a certificate to check its current status on the official IECEx register.

Complete units
CertificateEquipmentMarkingLatest issueVerify
IECEx SIR 11.0155XType ‘ST’ air conditioning units (HVAC) and Type ‘ST’ water chiller unitsStolway Pty LtdEx II* T* GbGroup, T class and ambient set for each unitIssue 5, 4 Aug 2026Verify IECEx SIR 11.0155X on the IECEx register (opens in a new tab)
IECEx KLCS 23.0007XAir conditioning units (HVAC), STCC cabinet cooler seriesStolway Manufacturing LLC, Abu DhabiEx 60079-46 II* T* GbGroup, T class and ambient set for each unitIssue 0, 31 May 2024Verify IECEx KLCS 23.0007X on the IECEx register (opens in a new tab)
Certified parts used inside our units
CertificateEquipmentMarkingLatest issueVerify
IECEx SIR 07.0095Compressor assemblyStolway Pty LtdEx db IIC T4…T3 GbIssue 4, 28 Nov 2023Verify IECEx SIR 07.0095 on the IECEx register (opens in a new tab)
IECEx SIR 10.0022XHeating element assemblyStolway Pty LtdEx e IIC T3 Gb or T5 GbIssue 1, 16 May 2022Verify IECEx SIR 10.0022X on the IECEx register (opens in a new tab)
IECEx TSA 07.0060XSolenoid coilStolway Pty LtdEx ma or Ex mb IIC T4Issue 3, 27 Jul 2020Verify IECEx TSA 07.0060X on the IECEx register (opens in a new tab)
IECEx KLCS 23.0009XRSR heater, models RSR TherM and RSR TherM-CStolway Manufacturing LLC, Abu DhabiEx db IIB+H2 T3 GbIssue 0, 31 Oct 2023Verify IECEx KLCS 23.0009X on the IECEx register (opens in a new tab)

Our systems are also ATEX certified. Ask us for the ATEX certificate and a copy of the certificate for each certified part fitted to your unit.

Hazardous Areas

How To Read An Ex Marking

The Ex marking on a nameplate tells you where the equipment may be installed. Here are typical markings on Stolway equipment, part by part.

Ex d e [ia] mb IIB+H2 T3 Gb

Typical Type ‘ST’ packaged unit
  1. ExExplosion protectedEquipment designed for use in explosive atmospheres.
  2. dFlameproofThe compressor, motors and control enclosure contain any internal explosion.
  3. eIncreased safetyJunction boxes and heaters are built so they can't spark or run hot.
  4. [ia]Intrinsically safe circuitsBarriers in the control enclosure limit sensor circuits to energy too low to ignite gas.
  5. mbEncapsulationSolenoid coils are sealed in compound; level "b" suits Zone 1.
  6. IIB+H2Gas group IIB plus hydrogenSuitable for IIA and IIB gases, and additionally hydrogen.
  7. T3Temperature class T3Maximum surface temperature 200 °C.
  8. GbEquipment protection level GbHigh protection: suitable for Zone 1 and Zone 2.

ATEX equivalent: II (1) 2 G Ex d e [ia] mb IIB+H2 T3. Each unit's nameplate carries its own marking, set by the certified parts fitted.

Ex 60079-46 IIB+H2 T4 Gb

STCC cabinet cooler
  1. ExExplosion protectedEquipment designed for use in explosive atmospheres.
  2. 60079-46Equipment assemblyAn assembly of individually certified parts, assessed as a whole under IEC TS 60079-46.
  3. IIB+H2Gas group IIB plus hydrogenSuitable for IIA and IIB gases, and additionally hydrogen.
  4. T4Temperature class T4Maximum surface temperature 135 °C.
  5. GbEquipment protection level GbHigh protection: suitable for Zone 1 and Zone 2.

Certified as an equipment assembly under IECEx KLCS 23.0007X.

Ex db IIC T4…T3 Gb Ta −20 °C to +60 °C

Stolway compressor assembly
  1. ExExplosion protectedEquipment designed for use in explosive atmospheres.
  2. dbFlameproof, level bThe enclosure contains any internal explosion; level "b" suits Zone 1.
  3. IICGas group IICThe most demanding gas group, including hydrogen and acetylene. Also covers IIA and IIB.
  4. T4…T3Temperature class T4 or T3135 °C or 200 °C, depending on the operating conditions.
  5. GbEquipment protection level GbHigh protection: suitable for Zone 1 and Zone 2.
  6. TaAmbient temperature rangeCertified for −20 °C to +60 °C around the equipment.

A certified part used inside our units, under IECEx SIR 07.0095.

Zones and equipment protection levels
ZoneEPLWhen it applies
Zone 0GaExplosive gas atmosphere present continuously or for long periods.
Zone 1Gb (or Ga)Explosive gas atmosphere likely to occur in normal operation.
Zone 2Gc (or Ga, Gb)Explosive gas atmosphere not likely in normal operation, and only briefly if it does occur.

Temperature classes (maximum surface temperature)

T1
450 °C
T2
300 °C
T3
200 °C
T4
135 °C
T5
100 °C
T6
85 °C

Compliance

Standards On Our Certificates

IEC 60079-0

Explosive atmospheres: equipment, general requirements

All certificates

IEC 60079-1

Equipment protection by flameproof enclosures "d"

Compressor assembly, RSR heater

IEC 60079-7

Equipment protection by increased safety "e"

Heating element assembly

IEC 60079-18

Equipment protection by encapsulation "m"

Solenoid coil

IEC TS 60079-46

Equipment assemblies

STCC cabinet coolers

ISO 80079-36 / -37

Non-electrical equipment for explosive atmospheres

STCC cabinet coolers

Need certificates for a project?

Tell us the unit or job number and we'll send the IECEx and ATEX certificates and the certificates for the parts fitted.

Request certificates